PRODUCTS

Elsec 30 Insulating Glove Class 3

ELSEC protective electrical insulating gloves are intended to be used exclusively for electrical purposes, as basic ppe for work under voltage up to 1kV, or as additional protective equipment for work under voltage higher than 1kV. 

  • These insulating gloves have been made to obtain high dielectric properties.
  • It enables to gain high quality and repeatability of the technical parameters.

ELSEC 30

  • *R – Resistance to acid, oil and ozone
  • *C – Resistance to extremely low temperature
  • 00/RC 0/RC 1/RC 2/RC 3/RC
  • Proof Test Voltage (r.m.s.) 2.5 kV 5 kV 10 kV 20 kV 30 kV
  • Max Working Voltage (a.c., r.m.s.) 0.5 kV 1 kV 7.5 kV 17 kV 26.5 kV
  • Min Alternating Withstand Test
  • Voltage, Effective Value: 5 kV 10 kV 20 kV 30 kV 40 kV
  • Max Leakage Current (routine test) < 12 mA to 18 mA
  • Glove’s Thickness 0.8 mm to 2.9mm (Depends on Class)
  • Min Tensile Strength 14 mPa 
Type ELSEC 2,5 ELSEC 5 ELSEC 10 ELSEC 20 ELSEC 30
Catalogue number S5911000 S5912000 S5913000 S5914000 S5915000
Class/Category, acc. to EN 60903:2003 + AC2:2005 00/RC 0/RC 1/RC 2/RC 3/RC
Designation of maximum use voltage AC, V rms 500 1 000 7 500 17 000 26 500
DC, V 750 1 500 11 250 25 500 39 750


AC tests
Proof voltage kV, rms 2,5 5 10 20 30
Maximum proof test current, mA, rms, (routine test) 12 12 14 16 18
Withstand test voltage kV, rms 5 10 20 30 40
Type ELSEC 2,5 ELSEC 5 ELSEC 10 ELSEC 20 ELSEC 30
Catalogue number S5911000 S5912000 S5913000 S5914000 S5915000

DC tests
Proof test voltage Avg kV 4 10 20 30 40
Withstand test voltage Avg kV, 8 20 40 60 70
Length, mm 360 360 360 360 360
Size 8, 9, 10,
11,12
8, 9, 10,
11,12
8, 9, 10,
11,12
8, 9, 10,
11,12
9,10, 11,12
Cuff Straight Straight Straight Straight Straight
-CE EN60903.
-ISO 9001: 2000 

Sign Up For Newsletters

Get E-mail updates about our latest shop and special offers.